Solar Battery Backup Calculator for Critical Loads
Solar battery backup calculator: enter battery watt-hours, usable capacity, inverter efficiency and critical load to estimate backup hours and required capacity.
How the result changes
Only nominal battery energy changes; all other inputs stay at your current values. The line illustrates the formula across the shown range. This is not a forecast of real-world outcomes.
About this calculation
A solar battery can run selected household loads when grid power fails, but panel size and battery size answer different questions. This solar battery backup calculator estimates how long an already charged battery can support a measured average critical AC load when no new solar energy arrives. It also estimates the nominal battery watt-hours needed for a chosen duration. The model exposes usable depth of discharge and inverter efficiency rather than silently assuming all label energy reaches the outlets.
Formula
E_AC = E_nominal×DOD/100×η/100; t = E_AC/P_load; E_required = P_load×t_target/(DOD/100×η/100)
Worked example
With Nominal battery energy: 5000 Wh, Usable depth of discharge: 80 %, DC-to-AC inverter efficiency: 90 %, Average critical AC load: 400 W, Target backup time: 12 h, estimated backup without new solar input is 9 h.
Separate stored energy from appliance power
Battery capacity is energy, normally watt-hours or kilowatt-hours; a load rating in watts is a rate of energy use. Multiply kilowatt-hours by 1,000 before entering watt-hours. Add the average watts of the refrigerator, router, lighting or other critical devices that actually run during an outage. A refrigerator may cycle, so a measured average over representative hours is more useful than its momentary nameplate reading. The inverter must separately support simultaneous running and startup power; sufficient stored energy alone does not establish that it can start a motor.
Account for usable capacity and conversion loss
The usable depth-of-discharge entry is the share of nominal battery energy available under the operating limit you choose. Inverter efficiency converts that available DC energy into estimated AC energy. National Renewable Energy Laboratory examples have used 80% depth of discharge and 90% inverter efficiency, but these are illustrative assumptions, not universal product specifications. If a manufacturer already states usable AC energy, do not subtract the same losses a second time. Battery age, temperature and protective reserves may further change available capacity.
Worked 5 kWh battery scenario
With a nominal 5,000 Wh battery, 80% usable discharge and 90% inverter efficiency, modeled energy at AC outlets is 5,000 × 0.80 × 0.90 = 3,600 Wh. At a steady 400 W critical load, the no-sun estimate is nine hours. To plan for twelve hours at that load and those same factors, 400 × 12 ÷ 0.72 gives about 6,667 Wh of nominal battery capacity. A second scenario with an 800 W average load halves the nine-hour runtime. This shows why identifying loads is as important as selecting a battery.
What solar generation changes
This is a battery-only outage estimate. Daytime photovoltaic production can extend runtime, but clouds, snow, shading, season, panel orientation and controller behavior make a fixed solar contribution unreliable as a single number. Whether an existing grid-tied solar array can operate during an outage depends on its backup hardware and configuration. Use a separate hourly solar-and-load model for multi-day autonomy and review how the system manages charging, islanding and load shedding. Do not add the panels’ rated watts directly to stored watt-hours.
Check the hardware before relying on the number
Confirm output rating, startup surge, transfer behavior, battery chemistry, manufacturer usable-energy definition and installation requirements. Critical medical or safety equipment needs a verified backup plan rather than a simple estimate. NREL notes that actual outage duration depends on charge at the outage start, solar production and the household load profile. Run low- and high-load scenarios, retain a reserve and use the manufacturer data for final equipment selection.
Common questions
Does this include sunlight during the outage?
No. It reports battery-only duration with no new photovoltaic input. Sunlight may extend backup, but the amount varies by hour and weather.
Can I enter 5 for a 5 kWh battery?
No. The field uses Wh, so enter 5,000. Entering 5 would represent only five watt-hours.
Sources and references
Inputs
- Nominal battery energy (Wh)
- Usable depth of discharge (%)
- DC-to-AC inverter efficiency (%)
- Average critical AC load (W)
- Target backup time (h)