Home Heat Loss Calculator

Home heat loss calculator for wall, window and roof U-values, heated volume, outdoor air changes and winter design temperature.

Home Heat Loss Calculator

Envelope transmission loss2,670.8 W
Outdoor-air replacement loss871.2 W
Estimated design-hour total3,542 W

About this calculation

A home heat loss estimate describes the rate at which heat leaves a building at a specified indoor and outdoor temperature, not the energy used over a whole winter. This calculator adds conductive losses through three groups of exposed surfaces to a simplified outdoor-air replacement term. Every area and U-value is editable, because insulation, windows, house geometry and climate differ. The output is useful for scenario comparisons and a first discussion of heating capacity; it is not a room-by-room professional heat-load study.

Formula

ΔT = T_in − T_out; Q_env = ΔT × Σ(U × A); Q_air ≈ 0.33 × V × ACH × ΔT; Q_total = Q_env + Q_air

Worked example

With Exposed opaque wall area: 180 m², Wall U-value: 0.35 W/(m²·K), Window and door area: 24 m², Window/door U-value: 1.6 W/(m²·K), Exposed roof or ceiling area: 100 m², Roof/ceiling U-value: 0.2 W/(m²·K), Heated indoor air volume: 240 m³, Outdoor air changes per hour: 0.5 ACH, Indoor design temperature: 20 °C, Outdoor design temperature: -2 °C, envelope transmission loss is 2,670.8 W.

Measure exposed areas without double-counting

Enter opaque wall area after subtracting windows and doors. Put glazing and exposed doors into the separate opening area, and roof or top ceiling into its own area. The tool does not currently include an exposed ground floor, garage boundary or thermal bridge as a separate field; if one is significant, obtain a more complete heat-loss assessment. Use U-values in watts per square metre per kelvin for the whole assembly, not R-values or insulation thickness. A lower U-value means lower heat flow at the same area and temperature difference. Compare like-for-like products and assembly descriptions.

Set the temperature and air-change assumptions

The difference between indoor and outdoor design temperatures drives both terms. Use a local cold-weather design condition rather than the absolute record minimum unless the project specifically requires that extreme. The air-replacement term uses an approximate volumetric heat capacity of 0.33 Wh per cubic metre per kelvin, multiplied by heated volume and hourly outdoor-air changes. ACH must describe effective exchange with outside air, not an unqualified blower-door test value measured at a pressure difference. A heat-recovery ventilator can reduce sensible ventilation loss, which this simple model does not separately represent.

Worked house example

For 180 m² of wall at U 0.35, 24 m² of openings at U 1.6, and 100 m² of roof at U 0.2, the envelope conductance is 63 + 38.4 + 20 = 121.4 W/K. At 20°C indoors and −2°C outside, transmission loss is 2,670.8 W. With 240 m³ of heated volume and 0.5 effective ACH, the outdoor-air term is 0.33 × 240 × 0.5 × 22 = 871.2 W. Together the estimate is 3,542 W, or about 12,086 BTU/h. Changing the outdoor design temperature changes the result proportionally in this simplified steady-state model.

Do not confuse the estimate with equipment selection

Real heating design checks each room, solar and internal gains, ground losses, air leakage pathways, intermittent operation and local standards. U-values for windows are commonly rated for a whole product under specified conditions. Thermal bridges and wet or poorly installed insulation can shift actual performance. A heating device also has output characteristics that vary with temperature and system settings. Use this estimate to see which assumptions dominate and to prepare a more informed conversation with a qualified designer, not as a final boiler or heat-pump size.

Common questions

Is this the number of kWh my house will use this month?

No. Watts are an instantaneous heat-loss rate at the entered design temperatures. Monthly energy requires temperature and operating time over the period.

Can I enter a blower-door ACH50 result directly?

No. ACH50 is measured at an imposed pressure difference and is not the effective outdoor air-change rate assumed here.

Sources and references

Inputs

  • Exposed opaque wall area (m²)
  • Wall U-value (W/(m²·K))
  • Window and door area (m²)
  • Window/door U-value (W/(m²·K))
  • Exposed roof or ceiling area (m²)
  • Roof/ceiling U-value (W/(m²·K))
  • Heated indoor air volume (m³)
  • Outdoor air changes per hour (ACH)
  • Indoor design temperature (°C)
  • Outdoor design temperature (°C)