HVAC Duct Size Calculator
HVAC duct size calculator: enter airflow in CFM and design velocity to compare round diameter with rectangular inside height.
How the result changes
Only design airflow changes; all other inputs stay at your current values. The line illustrates the formula across the shown range. This is not a forecast of real-world outcomes.
About this calculation
An HVAC duct size calculator can quickly turn a chosen airflow and air velocity into a geometric cross-section. This version is deliberately a first-pass sizing worksheet: it shows the inside area, equivalent circular diameter and height of a rectangle at the entered width. Real duct design also depends on pressure loss, fitting resistance, noise, available blower pressure and the distribution to each room. Enter a design CFM from an actual load and airflow plan, rather than assuming floor area alone determines the duct.
Formula
A = CFM / v; D = 12 × √(4A/π); H = 144A/W
Worked example
With Design airflow: 400 CFM, Chosen air velocity: 600 ft/min, Rectangular duct inside width: 12 in, required internal cross-sectional area is 96 in².
Start with design airflow in CFM
CFM means cubic feet of air per minute. A branch, return and main trunk will carry different flows, so use the flow appropriate to the section you are sizing. If the equipment or room airflow target is unknown, this calculator cannot create it from a duct width. ENERGY STAR’s HVAC design guidance treats load calculation, equipment selection and duct design as connected tasks. An arbitrary airflow inserted merely to obtain a familiar diameter can hide an undersized system. Verify whether the air volume is specified at actual operating conditions and whether several branch flows have already been added.
Choose velocity before solving geometry
Cross-sectional area in square feet is CFM divided by feet per minute. A larger target velocity produces a smaller duct area, but it may also increase friction and noise. This calculator does not choose a universally correct velocity; the user enters one as a design assumption. The round diameter is calculated from the area of a circle, while rectangular height is area divided by the specified internal width. Use clear inside dimensions, not a metal sheet’s outside size or a nominal dimension that includes lining.
Worked example for a 400 CFM branch
At 400 CFM and a chosen 600 ft/min, required area is 400 ÷ 600 = 0.667 ft², or 96 in². A circle with that area has an inside diameter of about 11.06 inches. If the duct must fit a 12-inch inside width, the corresponding inside height is 96 ÷ 12 = 8 inches. A commercially available nominal size may differ from either exact number; rounding a duct down changes velocity and pressure drop. Recalculate using the actual selected inside area rather than treating 11.06 inches as an off-the-shelf product.
Why a full duct design still matters
Long runs, elbows, transitions, grilles, filters and flexible duct alter static pressure. The blower may not deliver its nominal CFM through the proposed installation. Return ducts and supply branches also have different comfort and acoustic goals. A professional design checks equivalent length, friction rate, room-by-room flow, leakage, insulation and commissioning. The geometry here is useful for exploring a size range or checking arithmetic in a design discussion, but does not certify an installation or replace applicable HVAC methods and local code.
Common questions
Does a matching area mean a rectangular and round duct perform identically?
No. Equal area gives the same average velocity at the same airflow, but perimeter, friction and fittings change pressure loss.
Can this calculator select a blower or fan?
No. It takes design airflow as an input and does not calculate the system pressure curve or equipment performance.
Sources and references
Inputs
- Design airflow (CFM)
- Chosen air velocity (ft/min)
- Rectangular duct inside width (in)