Tankless Water Heater Sizing Calculator
Tankless water heater sizing calculator for simultaneous fixture flow, cold-water temperature, target outlet temperature and efficiency.
How the result changes
Only simultaneous shower flow changes; all other inputs stay at your current values. The line illustrates the formula across the shown range. This is not a forecast of real-world outcomes.
About this calculation
Tankless heater size is a two-dimensional question: how many gallons per minute must flow at once, and by how many degrees must the water be heated? A high advertised flow rate at a small temperature rise may not describe a cold-winter installation. Enter the coldest relevant inlet temperature, your desired outlet setting and the hot-water flows likely to coincide. The calculator gives a heat-rate estimate to compare with a manufacturer performance table, not a brand or model selection.
Formula
G = G_shower + G_sink + G_other; ΔT = T_out − T_in; Q = 500.4 × G × ΔT BTU/h; P_input = Q / η
Worked example
With Simultaneous shower flow: 2 US gal/min, Simultaneous sink flow: 1 US gal/min, Other simultaneous hot-water flow: 0 US gal/min, Cold inlet water temperature: 50 °F, Desired outlet temperature: 120 °F, Assumed operating efficiency: 90 %, peak simultaneous hot-water flow is 3 US gal/min.
Add fixtures that truly run at the same time
Measure a shower or tap at its normal setting if possible, or use a reliable fixture specification. Add only simultaneous hot-water demand; the shower and kitchen sink fields are convenient labels, while the other field can hold a washer or another fixture. If two showers may run together, include both in the shower total. A low-flow fixture may consume less than a generic rating, but a bathtub fill can be much higher. The U.S. Department of Energy advises using the practical maximum flow together with the required temperature rise when sizing a tankless unit.
Use cold-season inlet water, not a warm-day guess
The difference between outlet and inlet temperatures is the required rise. An inlet at 50°F and outlet at 120°F gives a 70°F rise. A colder 40°F supply would require 80°F for the same outlet setting, increasing required power by about 14%. If the desired outlet is not above the inlet, this heating model is invalid and the calculator asks for a correction. Use the temperature at the heater feed, not room air. Consider safe outlet settings and any mixing valve or appliance-specific requirements separately.
Worked example and product comparison
A 2.0 gpm shower and 1.0 gpm sink require 3.0 gpm together. At a 70°F rise, heating the water takes approximately 500.4 × 3 × 70 = 105,084 BTU/h, or 30.8 kW delivered to the water. At an assumed 90% operating efficiency, fuel input would be about 116,760 BTU/h. Read the manufacturer’s rated flow at a 70°F rise rather than comparing only a maximum GPM printed for milder conditions. Electric models have electrical service and circuit constraints; gas models have gas-supply and venting constraints.
Understand what the arithmetic excludes
The heat-rate estimate does not check minimum activation flow, pressure loss, pipe length, delivery delay, scale buildup, ventilation, freeze protection or local plumbing rules. Efficiency is an explicit assumption, not a guarantee that a product runs at exactly that percentage under all flows. Multiple fixtures may be supplied with different mixes of hot and cold water, so measured actual hot-water flow is better than assuming every outlet runs entirely hot. Before buying, compare the full winter flow-and-rise pair with manufacturer curves and ask an installer to verify utilities and safety provisions.
Common questions
Can I choose a tankless unit from its maximum GPM alone?
No. Maximum GPM is associated with a temperature rise. Compare the flow you need at your cold-season rise on the manufacturer performance curve.
Why does the result show both kW and BTU/h?
The heat delivered to water is displayed in kW. The input estimate in BTU/h includes the chosen efficiency and helps compare fuel-fired equipment ratings.